Steam generator operational inspection process
Contact Info
- Add:陕西省渭南市临渭区经济技术开发区前进路北段, Zip:
- Contact: 范高峰
- Tel:0913-2584118
- Email:2847916676@qq.com
Other Products
1. Check that the outlet water temperature, return water temperature, and pressure of the Shaanxi steam generator are normal and stable, and that combustion is good;
2. Check that the feed pump and standby pump are functioning properly;
3. Check that the pressure gauge, thermometer, and flow meter are undamaged;
4. Perform testing and treatment of the Shaanxi steam generator water quality, requiring that the makeup water has suspended solids≤20mg/h, total hardness≤216mg/h,pH(25℃)≥1, oil content≤2mg/h,and circulating waterpH=10~12;
5. Open the blowdown valve at regular intervals daily to discharge scale from the boiler.
6. The boiler should be shut down immediately under the following circumstances:
(1) When the outlet water temperature rises sharply and the difference from the corresponding saturation temperature under operating pressure is less than 20°C, or when vaporization has been detected;
When both the circulating water pump and the feed pump fail;
(2) When the pressure gauge, thermometer, and safety valve all fail;
(3) When components of the Shaanxi steam generator are damaged and pose a risk to operating personnel;
(4) When the feed pump continuously supplies water to the boiler, but the boiler pressure continues to drop;
(5) When a heating surface bursts and the outlet pressure cannot be maintained;
(6) When gas continues to be supplied after the boiler flame is extinguished.